• Disable (default)
Remote control
Allows the UPS to be controlled remotely via the CLI or RDU101 card.
• Enable (default)
• Disable
Any mode shutdown auto restart enable
Automatically restart the UPS after an Any mode shutdown signal is received. When the UPS is shut down via dry
contact inputs 1 or 2, it will restart automatically if this option is enabled.
• Enable
• Disable (default)
Output contact NO/NC
Selects the states of the dry contact outputs 5 and 6.
• Normally open (default)
• Normally closed
Input contact NO/NC
Selects the states of the dry contact inputs 1 and 2.
• Normally open (default)
• Normally closed.
Dry contact 5 (Output)
Selects the output of dry contact 5.
• Low battery — The contacts switch when the UPS reaches the amount of time left on battery configurable
from Low battery time (default)
• On bypass — The contacts switch when the UPS is running in bypass mode
• On battery — The contacts switch when the UPS is running on battery
• UPS fault — The contacts switch when a UPS fault has occurred
Dry contact 6 (Output)
Selects the output of dry contact 6.
• Low battery — The contacts switch when the UPS reaches the amount of time left on battery configurable
from Low battery time.
• On bypass — The contacts switch when the UPS is running in bypass mode
• On battery — The contacts switch when the UPS is running on battery
• UPS fault — The contacts switch when a UPS fault has occurred (default)
Dry contact 1 (Input)
Selects the action taken by the UPS when the input of dry contact 1 is triggered.
• Disable (default)
5 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp. 47
Vertiv™ Liebert® GXT5 UPS Installer/User Guide