Time
Select the current time for the UPS display, HH:MM:SS. See Setting the Date and Time on page56.
Display orientation
Selects the orientation of the display for use in rack or tower configuration.
Auto-rotate Automatically rotates based on the detected orientation of the UPS. (default)
Horizontal Screen rotated for rack use.
Vertical Screen rotated for tower use.
Audible alarm
If enabled, the UPS will beep when an alarm is generated. If disabled, it will be silent. See Audible Alarm (Buzzer)
on page63.
Enable (default)
Disable
Change settings password
Opens the dialog to change the password used to access and update the UPS parameter settings, see Changing
the Password on page55.
System Parameter Options
Auto restart
Allows the automatic restart of the UPS when input power is restored after a complete shutdown of the UPS due
to battery end of discharge (EOD).
Enable The UPS will restart automatically when the input power is restored after EOD. (Default)
Disable The UPS will not restart automatically
Auto restart delay
Length of time to elapse before an automatic restart after input power is restored.
0 - 999 seconds (default 0)
Guaranteed shutdown
Forces a continued shutdown of the UPS after the Low Battery alarm threshold is reached, even if input power is
restored during this time. This can be used to ensure connected equipment shuts down completely after
receiving a signal to shutdown from an external monitoring device before power is re-applied. This ensures that
once the equipment begins to shut down, it is brought down completely before power is applied again.
Enable
Disable (default)
Start with no battery
Allows the UPS to start when the battery is not installed or is not functional due to damage. This can be used to
turn on the UPS and power the attached load without battery protection when utility power is available but
battery backup is not.
Enable
46 Proprietary and Confidential ©2024 Vertiv Group Corp. 5 Operation and Display Panel
Vertiv™ Liebert® GXT5 UPS Installer/User Guide

Table of Contents

Other manuals for Vertiv LIEBERT GXT5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv LIEBERT GXT5 Series and is the answer not in the manual?

Vertiv LIEBERT GXT5 Series Specifications

General IconGeneral
ModelLIEBERT GXT5 Series
Product TypeUPS
TopologyDouble Conversion Online
DisplayLCD
Form FactorTower, Rackmount
Output Voltage200/208/220/230/240 VAC
Output Frequency50/60Hz ±0.1Hz (battery mode)
Typical Backup TimeVaries by model and load
Communication PortsUSB, RS-232
Operating Temperature0°C to 40°C (32°F to 104°F)
Relative Humidity0% to 95% (non-condensing)
DimensionsVaries by model
WeightVaries by model
CertificationsUL, cUL, CE, RoHS
Battery TypeValve Regulated Lead Acid (VRLA)