Model GXT5 5000MVRT4UXLN 6000MVRT4UXLN 8000MVRT6UXLN 10KMVRT6UXLN 15KMVR-T11UXLN 20KMVR-T11UXLN
Rating 5000VA/5000W 6000VA/6000W 8000 VA/8000 W 10000VA/10000W 15000VA/15000W 20000VA/20000W
Operating
Elevation
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating
Audible
Noise
<50 dBA,at 3.2 ft (1 m) from the front and sides, <55 dBA, at 3.2 ft (1 m) from rear
<58 dBA,at 3.2 ft (1 m) from the front and
sides
Agency
Safety UL1778, c-UL listed
RFI/EMI FCC Part 15 (Class A)
EMC IEEE/ANSI C62.41 Category B
Surge
Immunity
IEEE/ANSI C62.41 Category B
Transportat
on
ISTA Procedure 1A
Table 8.1 UPS Specifications, 5 kVA to 10 kVA Models (continued)
Model PD5 HDWR-MBS 001 002 003 004 005 006 007
Dimensions, D×W×H, in. (mm)
Unit 5.2 x 15.5 x 3.5 (132 x 394 x 89)
Shipping 9.5 x 20.7 x 9.1 (560 x 250 x 200)
Weight, lb.(kg)
Unit 6 (2.7) 8.8 (4.0) 8.6 (3.9) 9.9 (4.5) 10.6 (4.8) 9.5 (4.3)
Shipping 8.2 (3.7) 11 (5) 10.8 (4.9) 12.1 (5.5) 12.8 (5.8) 11.7 (5.3)
Electrical Specifications
Rating when
installed on 5
kVA
Factory default 5000VA/4500W
Rating when
installed on 6
kVA
Factory default 6000VA/5100W
Input power
connection
Hard-wired terminal block 3W + G
(L-L-N-G)
(1) L14-30P on a 10.5 ft (3.2 m) cord (1)
Output power
connection
Hard-wired terminal block 3W + G
(L-L-N-G)
(4)
5-20R
(1)
L14-30R
(1)
L6-30R
(2)
5-20R
(2)
L6-20R
(4)
5-20R
(2)
L6-30R
(4)
L5-20R
(2)
L5-30R
(4)
L5-20R
(2)
L6-30R
(4)
L6-20R
(2)
L5-20R
(2)
L6-20R
Table 8.2 POD Specifications for 5 kVA to 6 kVA Models
8 Specification Proprietary and Confidential ©2024 Vertiv Group Corp. 67
Vertiv™ Liebert® GXT5 UPS Installer/User Guide