19. Technical specifications
19.1. Technical specifications
Color Control GX
(1)
Power supply voltage range 8 - 70V DC
Current draw @
Display off
Display at minimum intensity
Display at maximum intensity
12V DC 24V DC 48V DC
140mA 80mA 40mA
160mA 90mA 45mA
245mA 125mA 65mA
Potential free contact 3A / 30V DC / 250V AC (Normally open)
Communication ports
VE.Direct 2 separate VE.Direct ports – isolated
VE.Can 2 paralleled RJ45 sockets – isolated
VE.Bus 2 paralleled RJ45 sockets – isolated
USB 2 USB Host ports – not isolated
Ethernet 10/100/1000MB RJ45 socket – isolated except shield
3rd party interfacing
Modbus-TCP Use Modbus-TCP to monitor and control all products connected to the Color Control GX
JSON Use the VRM JSON API to retrieve data from the VRM Portal
Other
Outer dimensions (h x w x d) 130 x 120 x 28mm
Operating temperature range -20 to +50°C
Standards
Safety EN 60950-1:2005+A1:2009+A2:2013
EMC EN 61000-6-3, EN 55014-1, EN 61000-6-2, EN 61000-6-1, EN 55014-2
Automotive E4-10R-053535
(1)
For more detailed information about the Color Control GX, please visit the Victron GX product range page.