Serie 750, 753 Planning
System manual | Version: 3.0.2 35
Example of a Power Supply Concept for Marine Applications - Class A and B per
DNV GL
U
S
U
F1
U
F2
1
2 3
4
U
F3
5
Figure16: Power Supply Concept for Marine Applications – Class A and B
1 Filter module, 24VDC, HI GF (750-626/020-002) or
filter module, 24VDC, HI (750-626/020-000) or
filter module, 24VDC, HI / T (750-626/025-001)
2 Bus supply module, 24VDC (750-602) or
bus supply module, 24VDC, with fuse (750-601) or
bus supply module, 24VDC, with fuse and diagnostics (750-610)
3 Filter module, 24VDC, HI GF 750-624/020-002 or
filter module, 24VDC, HI 750-624/020-000
4 Distance module, 24 VDC / 230 VAC (750-616/030-000)
5 Bus supply module, 230VAC/DC, with diagnostics, with fuse holder (750-611) or
bus supply module, 230VAC/DC, without diagnostics, with fuse holder (750-609) or
bus supply module, 230VAC/DC, without diagnostics, without fuse holder (750-612)
U
S
System supply (24VDC)
U
F1
Field supply 1 (24VDC)
U
F2
Field supply 2 (24VDC)
U
F3
Field supply 3 (230VAC)
Power Supply with FE Power Jumper Contact
If an FE power contact is required after the filter module (750-626/xxx-xxx), an additional
supply module is required after the filter module. To do this, the field supply from the filter
module (750-626/xxx-xxx) must be bridged to the supply module.

Table of Contents

Other manuals for WAGO 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750 Series and is the answer not in the manual?

WAGO 750 Series Specifications

General IconGeneral
Protection ClassIP20
Bus CouplersPROFIBUS, CANopen, Ethernet
ModulesDigital Input, Digital Output, Analog Input, Analog Output
MountingDIN rail mounting
Voltage Supply24 V DC (typical)
Communication ProtocolDepends on the bus coupler (e.g., PROFIBUS, CANopen, DeviceNet, Ethernet)
Digital Input ChannelsVaries by module (e.g., 8, 16 channels)
Digital Output ChannelsVaries by module (e.g., 8, 16 channels)
Analog Input ChannelsVaries by module (e.g., 2, 4, 8 channels)
Analog Output Channels1, 2, 4 channels (depending on module)
Width12 mm, 24 mm (typical module widths)
Number of ChannelsVaries by module type
Current Consumption per ChannelVaries by module type

Related product manuals