Offer adequate protection against direct or indirect contact.
Offer adequate protection against UV irradiation.
Restrict access to authorized personnel and may only be opened with tools.
Ensure the required pollution degree in the vicinity of the system.
Prevent fire from spreading outside of the enclosure.
Guarantee mechanical stability.
4.2.2 Overcurrent Protection
System and field supply are through the head station and/or additional supply modules.
Protect the power supply as specified in the technical product data. Use:
Supply modules with integrated fuses
External fuses
You can find more information in the & Product Manual.
4.2.3 Ground Conductor
The I/O system does not require a protective conductor connection for proper operation.
In addition, the I/O system does not provide any protective conductor functionality via the
field connections. If a protective conductor connection is required, it must be implemented
outside the system.
4.2.4 Buffering
To compensate for power interruptions per IEC 61131 (PS-1 or PS-2), external buffering
is required.
Buffer capacity depends on the node configuration, which is why it is not possible to pro-
vide general information on the required capacity.
4.2.5 Mounting Position
All specifications and handling steps refer to the nominal mounting position. Deviating
mounting positions affect, for example:
Air circulation
Measuring accuracy
Maintain the following clearances to adjacent components, cable ducts and the sides of
housings and frames for the entire node structure.

Table of Contents

Other manuals for WAGO 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750 Series and is the answer not in the manual?

WAGO 750 Series Specifications

General IconGeneral
Protection ClassIP20
Bus CouplersPROFIBUS, CANopen, Ethernet
ModulesDigital Input, Digital Output, Analog Input, Analog Output
MountingDIN rail mounting
Voltage Supply24 V DC (typical)
Communication ProtocolDepends on the bus coupler (e.g., PROFIBUS, CANopen, DeviceNet, Ethernet)
Digital Input ChannelsVaries by module (e.g., 8, 16 channels)
Digital Output ChannelsVaries by module (e.g., 8, 16 channels)
Analog Input ChannelsVaries by module (e.g., 2, 4, 8 channels)
Analog Output Channels1, 2, 4 channels (depending on module)
Width12 mm, 24 mm (typical module widths)
Number of ChannelsVaries by module type
Current Consumption per ChannelVaries by module type

Related product manuals