Serie 750, 753Planning
36 System manual | Version: 3.0.2
Figure17: Power Supply Concept for Marine Applications – Class A and B with FE Power Jumper Contact
1 Head station
2 Filter module, 24VDC, HI GF (750-626/020-002) or
filter module, 24VDC, HI (750-626/020-000) or
filter module, 24VDC, HI / T (750-626/025-001)
3 Bus supply module, 24VDC (750-602) or
bus supply module, 24VDC, with fuse (750-601) or
bus supply module, 24VDC, with fuse and diagnostics (750-610)
U
S
System supply (24VDC)
U
F1
Field supply 1 (24VDC)
FE Functional ground
4.5.2 Exi Applications
Some I/O modules are intended to be connected with devices located in hazardous ar-
eas. To ensure safety and reliability in these applications, several additional requirements
must be considered:
The node structure meets the additional requirements specified below for the power
supply as well as the requirements for air and creepage distances.
The operator obtains a prototype test certificate that confirms the correct installation of
the system and store it in a control cabinet or housing.
Observe the detailed requirements as stated in the original wording of the respective cer-
tificate (Installation Regulations Specified by Approvals).
Power Supply Requirements
Only Exi bus supply modules are permitted to be used for power supply to any node sec-
tions containing I/O modules for Exi applications.
The following Ex i potential supply modules may be used for this purpose: 750-606,
750-625/000-001.

Table of Contents

Other manuals for WAGO 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750 Series and is the answer not in the manual?

WAGO 750 Series Specifications

General IconGeneral
Protection ClassIP20
Bus CouplersPROFIBUS, CANopen, Ethernet
ModulesDigital Input, Digital Output, Analog Input, Analog Output
MountingDIN rail mounting
Voltage Supply24 V DC (typical)
Communication ProtocolDepends on the bus coupler (e.g., PROFIBUS, CANopen, DeviceNet, Ethernet)
Digital Input ChannelsVaries by module (e.g., 8, 16 channels)
Digital Output ChannelsVaries by module (e.g., 8, 16 channels)
Analog Input ChannelsVaries by module (e.g., 2, 4, 8 channels)
Analog Output Channels1, 2, 4 channels (depending on module)
Width12 mm, 24 mm (typical module widths)
Number of ChannelsVaries by module type
Current Consumption per ChannelVaries by module type