42 Function Description WAGO-I/O-SYSTEM 750
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
The decisive factor is the maximum representable current value in the process
image.
If the transformation ratio is 500:1 A, for example, the resulting D-CTR of 500
cannot be taken into account in the I/O module 750-493 (1A) directly via active
user scaling, likewise a D-CTR of 100 at a transformation ratio of 500:5 A in
750-493/000-001 (5A).
Therefore, the following setting options and calculations for the measured values
result in the process image for the current-dependent variables:
A. User Scaling OFF, Measurement without Current Transformer