WAGO-I/O-SYSTEM 750 Function Description 43
750-493 3-Phase Power Measurement Module
Manual
Version 1.2.0
B. User Scaling ON, Measurement with Current Transformer
Measured value = Process value x Scaling factor PI
Measured value = Process value x Scaling factor PI
Measured value = Process value x Scaling factor PI
* Register 35: Setting in the register defines the scaling factor PI for energy values
C. User Scaling OFF, Measurement with Current Transformer 500:1 A
(1A Variants) and 500:5 A (5A Variants)
D-CTR values of 500 or 100 must be taken into account externally when user
scaling is OFF, i.e. the transferred measured value must be multiplied by 500 or
100 in the high-level PLC.
Measured value = Process value x Scaling factor PI
x D-CTR
Note: Resolution of the current values in 500mA steps