The absolute minimum pressure on the outlet side.
This value is automatically calculated based on the
relative minimum pressure and the current setpoint.
Behaviour in the event of minimum pressure
OFF (Stop)
ON (Cont)
Delay maximum pressure signal
0 … 20 … 60
Delay minimum pressure signal
0 … 20 … 60
SCe NWB
The threshold for detecting a dry run via the supply
pressure sensor. If the threshold is greater than the
threshold in menu 5.4.7.0., the 5.4.7.0. threshold is
set to the value of this threshold.
-1.0 … 1.2 … sensor
measurement range
SCe NWB
The threshold for resetting after a dry run is
detected via the supply pressure sensor. The
threshold must be greater or equal to the 5.4.6.0.
threshold. If the threshold is smaller than the
threshold in menu 5.4.6.0., the 5.4.6.0. threshold
is set to the value of this threshold.
-1.0 … 1.5 … sensor
measurement range
Signal output parameters
The behaviour of the collective run signal Ready
Run
Valid until Display
Description
Parameter range
Factory setting