Installation and operating instructions Wilo-Control SC-Booster (SC, SC-FC, SCe) 51
40035
(34)
Pump status 3 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31,000
40036
(35)
Pump status 4 BITMAP 0: Auto
1: Manu
2: Disabled
3: Running
4:
5: Error
R 31,000
40041
(40)
Pump mode 1 ENUM 0. Off
1. Hand
2. Auto
RW 31,000
40042
(41)
Pump mode 2 ENUM 0. Off
1. Hand
2. Auto
RW 31,000
40043
(42)
Pump mode 3 ENUM 0. Off
1. Hand
2. Auto
RW 31,000
40044
(43)
Pump mode 4 ENUM 0. Off
1. Hand
2. Auto
RW 31,000
40062
(61)
General status BITMAP 0: SBM
1: SSM
R 31,000
40068
(67)
Setpoint 1 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31,000
40069
(68)
Setpoint 2 UINT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
RW 31,000
40074
(73)
Application ENUM 0. Booster
1. HVAC
2. WP
3. Lift
4. FFS-Diesel
5. FFS-Electro
6. FLA
7. Clean
8. Rain
R 31,101
40075
(74)
External setpoint INT16 0.1 bar
0.1 m
0.1 K
0.1 °C
0.1 psi
R 31,000
40076
(75)
Activate external
setpoint
BOOL RW 31,000
40077 –
40078
(76 – 77)
Number of switching-on
procedures of the system
UINT32 R 31,000
40079 –
40080
(78 – 79)
Switchgear data
operating hours
UINT32 1h R 31,000
40081 –
40082
(80 – 81)
Total switching cycles of
pump 1
UINT32 R 31,000
Holding
register
Name Data type Scaling
and unit
Elements Access Added