English
52 WILO SE 09/2018
Subject to technical changes!
40083 –
40084
(82 – 83)
Total switching cycles of
pump 2
UINT32 R 31,000
40085 –
40086
(84 – 85)
Total switching cycles of
pump 3
UINT32 R 31,000
40087 –
40088
(86 – 87)
Total switching cycles of
pump 4
UINT32 R 31,000
40097 –
40098
(96 – 97)
Total operating hours of
pump 1
UINT32 1h R 31,000
40099 –
40100
(98 – 99)
Total operating hours of
pump 2
UINT32 1h R 31,000
40101 –
40102
(100 – 101)
Total operating hours of
pump 3
UINT32 1h R 31,000
40103 –
40104
(102 – 103)
Total operating hours of
pump 4
UINT32 1h R 31,000
40139 –
40140
(138 – 139)
Fault status BITMAP32 0: Sensor error
1: P man
2: P min
3: FC
4: TLS
5: Pump 1 Alarm
6: Pump 2 Alarm
7: Pump 3 Alarm
8: Pump 4 Alarm
9: Pump 5 Alarm
10: Pump 6 Alarm
11: -
12: -
13: Frost
14: Battery low
15: High water
16: Priority off
17: Redundancy
18: Plausibility
19: Slave communication
20: Net supply
21: Leakage
R 31,000
40141
(140)
Acknowledge BOOL W 31,000
40142
(141)
Alarm history index UINT16 RW 31,000
40143
(142)
Alarm history
Fault number
UINT16 0.1 R 31,000
40147
(146)
Alarm histogram index UINT16 RW 31,000
40148
(147)
Alarm histogram
Fault number
UINT16 0.1 R 31,000
40149
(148)
Alarm histogram
Fault frequency
UINT16 R 31,000
Holding
register
Name Data type Scaling
and unit
Elements Access Added