Installation and operating instructions Wilo-Control SC-Booster (SC, SC-FC, SCe) 17
SCe NWB
(p-v)
The absolute pressure setpoint in the event of zero
flow. This value is automatically calculated based on
the relative setpoint in the event of zero flow.
0 … setpoint at Q
max
The menu for the pressure thresholds for the
activation and deactivation of pumps
The threshold for activation of the base-load pump
relative to the active setpoint
75 … 90 …100
The absolute threshold for activation of the base-
load pump. This value is automatically calculated
based on the relative threshold and the current
setpoint.
The threshold for switching off the base-load pump
relative to the active setpoint
100... 105 ... 125
The absolute threshold for switching off the base-
load pump. This value is automatically calculated
based on the relative threshold and the current
setpoint.
SC
SC…FC
The threshold for activation of the first peak-load
pump relative to the active setpoint
75 … 90 …100
SC
SC…FC
The absolute threshold for activation of the first
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
Valid until Display
Description
Parameter range
Factory setting