The threshold for switching off the first peak-load
pump relative to the active setpoint
100... 115 ... 125
SC
SC…FC
The absolute threshold for switching off the first
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
SC
SC…FC
The threshold for activation of the second peak-
load pump relative to the active setpoint
75 … 90 …100
SC
SC…FC
The absolute threshold for activation of the second
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
SC
SC…FC
The threshold for switching off the second peak-
load pump relative to the active setpoint
100... 110 ... 125
SC
SC…FC
The absolute threshold for switching off the second
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
SC
SC…FC
The threshold for activation of the third peak-load
pump relative to the active setpoint
75 … 90 …100
SC
SC…FC
The absolute threshold for activation of the third
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
Valid until Display
Description
Parameter range
Factory setting