Installation and operating instructions Wilo-Control SC-Booster (SC, SC-FC, SCe) 19
SC
SC…FC
The threshold for switching off the third peak-load
pump relative to the active setpoint
100... 105 ... 125
SC
SC…FC
The absolute threshold for switching off the third
peak-load pump.
This value is automatically calculated based on the
relative threshold and the current setpoint.
SCe (p-c)
SC…FC
Speed thresholds for activation and deactivation of
pumps
SCe (p-c)
SC…FC
Activation threshold of the peak-load pump(s)
based on the speed of the base-load pump
78 … 98 … f
max
-2
SCe (p-c)
SC…FC
Deactivation threshold of the peak-load pump(s)
based on the speed of the base-load pump
SCe:
f
min
+2 … 32 … 75
SC...FC:
f
min
+2 … 42 … 72
SCe
SC…FC
PID controller parameter menu
SCe
SC…FC
Proportional factor 0.1 … 2.0 … 100.0
SCe
SC…FC
Integral factor 0.0 … 0.3 … 300.0
Valid until Display
Description
Parameter range
Factory setting