13
2. For the Installer
2.4 Taking in
FireWIN is delivered without cladding (door, cover, side panels) on a pallet, without wood partitions. The cladding
parts are in a separate cardboard box. The taking-in weight is less than 200 kg, the taking-in width is 55 cm.
2.5 Installation
2.5.1 Installation room
Basically, any room with normal air humidity and living space temperature in the living area is suitable for instal-
lation, providing it has a flue connection with an adequate draught (see technical data for flue requirements) and
satisfies the statutory regulations and directives.
The installation room should not be too small otherwise the room could be overheated by the heat radiation. The
recommended rule of thumb is: The installation room should account for at least 15% of the area to be heated.
Note!
Due to the operating and flame noises, we do not recommend installing the device in bedrooms or
quiet rooms.
– The minimum service clearances from flammable materials and for connections, cleaning and maintenance
must be complied with – see point 2.6 Minimum service clearances.
– FireWIN must be placed directly on a non-flammable base plate (e.g. floor plate accessory).
– Sufficient ventilation of the set-up area must be assured see section 2.3 Verbrennungsluft
combustion air.
– The boiler may only be installed in a dry location.
– The boiler may not be installed in rooms that are very dusty or humid.
Permissible limit values: Air humidity: 85 % at 25°C room temperature (noncondensing)
Room temperature +2 to 40°C