Operation
40031/A1
Winterthur Gas & Diesel Ltd.
5/ 12
4.4.1 Passive Failures
1) To monitor the passive failures, connect an applicable resistor between
connections 2 and 3 of the pressure switches that follow:
D PS1101S
D PS2002S
D PS4341S.
The values of resistors that are related to the the different remote controls are given in
Table 3:
Table 3: Resistor Values
Supplier Resistor Power
KONGSBERG Maritime 10 0.6
NABTESCO 5.6 0.6
SAM / Lyngsø 8.2 0.6
4.4.2 Oil Mist Detector
1) To activate an alarm in the oil mist detection system, do the procedure given in
the Oil Mist Detector manual.
4.4.3 Speed Pick-ups
WARNING
Injury Hazard: Before you operate the turning gear, make sure
that no personnel are near the flywheel.
1) Do a check of the pick-ups for speed measurement as follows:
a) Engage the turning gear.
b) Use the turning gear to turn the crankshaft.
c) Make sure that the LEDs on the speed pick-ups come on and go off when the
TDC mark and a tooth (of the flywheel) move across the proximity sensor face.
d) Disengage the turning gear.
4.4.4 Level Switches
1) Do a check of the level switch in the condensate collectors as follows:
a) Manually operate the float switch to activate a high-level alarm.
2) Do a check of the level switch in the leakage oil return as follows:
b) Manually operate the float switch to activate a high-level alarm.
201708
Engine Control