4.9 WECS Critical Failure (WECS Engine Failure)
Failure Text ME crank angle #1+2 fail. (ID 1)
Indication FCM20 No. LED ID Display
#03 and #04 None 1 1
Cause The two crank angle sensor measurements fail.
Procedure Do a check of the crank angle sensor unit and terminal box E96 for damage.
In the terminal box E96, make sure that the cables and connections are connected correctly
and do not have damage.
If necessary, repair or replace damaged cables.
Use a multimeter to do a check of the power supply to the last and last but one FCM20.
It there is a power supply, do a check of the SSI-Bus terminating resistors (120 ohm) on plugs
X22 (terminals 51/52 and 53/54) and X23 (terminals 59/60 and 61/62) of FCM-20 #01. Make
sure that the resistors are connected correctly and there is no damage.
If a failure shows only on one FCM20, make sure that the cable connections on plugs X22
and X23 are serviceable.
Start a CAS trend in flexView.
If necessary, replace a minimum of one two crank angle sensor immediately.
Failure Text ME both CA / TDC high shift (ID 65)
FCM20 No. LED Failure ID Display
Indication #05 BI1 65 65
Cause The difference between the TDC pick-up (measured angle) and crank angle sensor#1 and
sensor#2 is more than 4_CA. this failure will cause an engine shutdown.
The crank angle sensor or toothed belt has moved.
Procedure In flexView, do a check for an incorrect TDC offset adjustment.
Adjust to get the correct distance of the TDC pick-up to the flywheel tooth (usually 4mm)
Make sure that the crankshaft has no deformation.
Do a check of the crank angle sensor drive and the belt for damage.
Make sure the the CAS#1 and CAS#2 are in the correct position (at TDC#1)
Start a CAS trend in flexView.
If necessary, replace a minimum of one of the two crank angle sensors immediately
Failure Text ME excessive engine speed (ID 69)
FCM20 No. LED Failure ID Display
Indication #03 and #04 None 69 69
Cause The engine has too much speed (more than 115% nominal speed).
Procedure Do a check of each alarm from the CA sensors
In heavy sea conditions, decrease the engine speed.
Do a check of related speed alarms in the safety system