EasyManuals Logo

Witt MFA 9000 User Manual

Witt MFA 9000
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
Page 44 of 46
WITT-GASETECHNIK GmbH & Co KG
Salinger Feld 4-8
: +49 (0)2302 89010
www.wittgas.com
Gas Safety- & Control Equipment
D-58454 Witten
Fax: +49 (0)2302 89013
witt@wittgas.com
9 Technical Data
Functional scheme number:
F830.405300 001
Date: 30.06.2011
1 sheet
Electrical circuit diagram number:
E830.405300 006
Date: 14.09.2015
2 sheets
Ansichtszeichnung-Nummer:
Setting up (usage):
Indoors
Soiling index:
3 (Industrial standard)
Temperatures (not-condensing):
Storage temperature :
min. -25 °C
max. 70 °C
Industrial standard
Ambient temperature:
min. -5 °C
max. 50 °C
Gas inlet temperature:
min. -5 °C
max. 50 °C
Operating altitude:
max. 2000 m above sea level
Dimensions (HxWxD) in mm:
235 x 240 x 230 without connections
Weight:
9.3 kg
Sensor Performance:
See Section 9.1.1
Sample gases:
See Section 9.1.2
Sample gas inlet pressure:
Inlet for pressurised gases:
min. 1.5 barg, dynamic
max. 20.0 barg, static
alternatively: Lance inlet (option):
un-pressurised
max. 0.3 barg, static
Calibration gas inlet pressure:
min. 1.5 barg, dynamic
max. 20.0 barg, static
Factory setting of
pressure regulator (65,66):
1.0 bar
Factory setting of
pressure regulator (49):
1.0 bar
Gas flows:
(at pressure settings given above)
Sensor about.:
1 l/min
Bypass (option) about.:
1 l/min
Gas inlet connections:
Continuous analysis:
WITTFIX for copper pipe OD 6 mm
alternatively: Lance inlet (option):
WITTFIX for copper pipe OD 6 mm
Gas outlet connections:
WITTFIX for copper pipe OD 6 mm
optional: bypass outlet:
WITTFIX for copper pipe OD 6 mm
Electrical supply voltage:
L/N/PE AC 50/60 Hz 100 - 240 V (-10%, +10% in acc. IEC 38)
Protection measures:
Protection class 1 (earth wire connection)
Power consumption:
max. 40 VA
Enclosure rating:
Corresponds to 20
Rating of the floating contacts
(optional):
max. 250 V AC, 24 V DC, max. 2 A
Corresponds to the protection re-
quirements of the directive:
Directive 2004/108/EC (electromagnetic compatibility),
Standards applied (design rules):
DIN EN 61000-6-3 2007-09, DIN EN 61000-6-2 2006-03
DIN EN 60439-1/2005-01

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Witt MFA 9000 and is the answer not in the manual?

Witt MFA 9000 Specifications

General IconGeneral
BrandWitt
ModelMFA 9000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals