VESDA-EVEP-A10-P Product Guide
58 www.xtralis.com
Command Description Execute From
A button
on the
Detector
Xtralis VSC
Software
Start AutoLearn Flow In Xtralis VSC you will be prompted to set the period
of time that the environment is monitored to allow
the system to decide what flow thresholds are most
appropriate.
When the AutoLearn has finished, the flow
thresholds are overwritten.
After AutoLearn is complete, review to confirm that
the thresholds are within ranges allowed by local
codes and standards.
Refer to Chapter 6 on page 77 for more information.
To initiate AutoLearn Smoke and Flow using the
internal AutoConfig button, press and hold the button
until the AutoConfig LEDstarts flashing
(approximately 15 seconds), then release the button.
Cancel AutoLearn Flow Cancels the AutoLearn Flow process.
Flow thresholds will remain at levels set prior to
commencing AutoLearn Flow.
To cancel AutoLearn Smoke and Flow functions
using the internal AutoConfig button, press and hold
the button for 5 seconds. The LED will turn off.
Start AutoLearn Smoke In Xtralis VSC you will be prompted to set the period
of time that the environment is monitored to allow
the system to decide what smoke thresholds are
most appropriate.
When the AutoLearn has finished, the smoke
thresholds are overwritten.
After AutoLearn is complete, review to confirm that
the thresholds are within ranges allowed by local
codes and standards.
Refer to Chapter 6 on page 77 for more information.
To initiate AutoLearn Smoke and Flow using the
internal AutoConfig button, press and hold the button
until the AutoConfig LEDstarts flashing
(approximately 15 seconds), then release the button.
Cancel AutoLearn
Smoke
Cancels the AutoLearn Smoke process.
Smoke thresholds will remain at levels set prior to
commencing AutoLearn Smoke.
To cancel AutoLearn Smoke and Flow functions
using the internal AutoConfig button, press and hold
the button for 5 seconds. The LED will turn off.
Rebuild Zone List Re-learns the list of display modules that are
assigned to the detector on the VESDAnet.
Start Major Fault Test Generates a major fault on the detector and de-
energizes the fault relay for 2 minutes.
Table5-2: Detector Commands (continued...)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xtralis VESDA-E VEP-A10-P and is the answer not in the manual?

Xtralis VESDA-E VEP-A10-P Specifications

General IconGeneral
BrandXtralis
ModelVESDA-E VEP-A10-P
CategorySmoke Alarm
LanguageEnglish

Related product manuals