7 Electrical Installation
YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation 43
Table 7.3 Recommended Wiring Tools
Screw Size Screw Shape Adapter
Bit
Torque Driver Model
(Tightening Torque)
Torque Wrench
Model Manufacturer
M4 Slotted (-) Bit SF-BIT-SL 1,0X4,0-70 PHOENIX CONTACT
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 in∙lb))
-
M5
*1
Slotted (-) Bit F-BIT-SL 1,2X6,5-70 PHOENIX CONTACT
Wire Gauge
25 mm
2
(AWG 10):
TSD-M 3NM
(1.2 - 3 N∙m
(10.6 - 26.6 in∙lb))
Wire Gauge
25 mm
2
(AWG 10): -
Wire Gauge
30 mm
2
(AWG 8): -
Wire Gauge
30 mm
2
(AWG 8):
4.1 - 4.5 N∙m
(36.3 - 39.8 in∙lb)
*2 *3
M6
Hex socket cap
(WAF: 5 mm)
Bit SF-BIT-HEX 5-50 PHOENIX CONTACT -
5 - 9 N∙m
(44.3 - 79.7 in∙lb)
*2 *3
Slotted (-) Bit SF-BIT-SL 1,2X6,5-70 PHOENIX CONTACT -
3 - 3.5 N∙m
(26.6 - 31.0 in∙lb)
*2 *3
M8
Hex socket cap
(WAF: 6 mm)
Bit SF-BIT-HEX 6-50 PHOENIX CONTACT -
8 - 12 N∙m
(70.8 - 106.2 in∙lb)
*2
*3
M10
Hex socket cap
(WAF: 8 mm)
Bit SF-BIT-HEX 8-50 PHOENIX CONTACT -
12 - 14 N∙m
(106.2 - 123.9 in∙lb)
*2
*3
*1 When wiring drive models 2056 and 4089 and smaller, select the correct tools for the wire gauge.
*2 Use 6.35 mm (0.25 in) bit socket holder.
*3 Use a torque wrench that can apply this torque measurement range.
Main Circuit Terminal Block Wiring Procedure
Remove the keypad and front cover before wiring the main circuit terminal block.
1. Pull the wiring cover away from the drive to remove it.
A - Wiring cover
Figure 7.6 Remove the Wiring Cover
2. Put the end of a prepared wire into the terminal block.
Figure 7.7 Install the Electrical Wire