11 Drive Control, Duty Modes, and Programming
72 YASKAWA TOEPC71061737B GA800 Drive Installation & Primary Operation
No.
(Hex.)
Name Description
H2-03
(040D)
Term M5-M6 Function Selection
Sets the function for MFDO terminal M5-M6.
H3-01
(0410)
Terminal A1 Signal Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
H3-02
(0434)
Terminal A1 Function Selection
Sets the function for MFAI terminal A1.
H3-03
(0411)
RUN
Terminal A1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A1.
H3-04
(0412)
RUN
Terminal A1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A1.
H3-05
(0413)
Terminal A3 Signal Level Select
Sets the input signal level for MFAI terminal A3.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
H3-06
(0414)
Terminal A3 Function Selection
Sets the function for MFAI terminal A3.
H3-07
(0415)
RUN
Terminal A3 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A3.
H3-08
(0416)
RUN
Terminal A3 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A3.
H3-09
(0417)
Terminal A2 Signal Level Select
Sets the input signal level for MFAI terminal A2.
0 : 0-10V (LowLim=0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
H3-10
(0418)
Terminal A2 Function Selection
Sets the function for MFAI terminal A2.
H3-11
(0419)
RUN
Terminal A2 Gain Setting
Sets the gain of the analog signal input to MFAI terminal A2.
H3-12
(041A)
RUN
Terminal A2 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A2.
H3-13
(041B)
Analog Input FilterTime Constant
Sets the time constant for primary delay filters on MFAI terminals.
H3-14
(041C)
Analog Input Terminal Enable Sel
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection] is
ON.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
H4-01
(041D)
Terminal FM Analog Output Select
Sets the monitor number to send from MFAO terminal FM.