Name LCD Display Description Values Page
H3-04
(0412)
Terminal A1 Bias
Setting
Terminal A1 Bias
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Default: 0.0%
Min.: -999.9
Max.: 999.9
183
H3-09
(0417)
Terminal A2 Signal
Level Selection
Term A2 Level
0: 0-10V,
(LowLim=0)
1: 0-10V, (BipolRef)
2: 4-20 mA
3: 0-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP Switch S1-2 to set input terminal A2 for
a current or voltage input signal.
Default: 2
Range: 0 to 3
184
H3-10
(0418)
Terminal A2 Function
Selection
Term A2 FuncSel
Sets the function of terminal A2. Default: B
Range: 0 to 41
184
H3-11
(0419)
Terminal A2 Gain
Setting
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Default: 100.0%
Min.: -999.9
Max.: 999.9
184
H3-12
(041A)
Terminal A2 Bias
Setting
Terminal A2 Bias
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Default: 0.0%
Min.: -999.9
Max.: 999.9
184
H3-13
(041B)
Analog Input Filter
Time Constant
A1/A2 Filter T
Sets a primary delay filter time constant for terminals A1 and
A2. Used for noise filtering.
Default: 0.03 s
Min.: 0.00
Max.: 2.00
184
H3-14
(041C)
Analog Input Terminal
Enable Selection
A1/A2 Sel
1: A1 Available
2: A2 Available
7: All Available
Determines which analog input terminals will be enabled when
a digital input programmed for “Analog input enable”
(H1-oo = C) is activated.
1: Terminal A1 only
2: Terminal A2 only
7: All terminals enabled
Default: 7
Range: 1, 2, 7
186
H3-16
(0440)
Terminal A1 Offset Term A1 Offset
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
Min.: -500
Max.: 500
185
H3-17
(0441)
Terminal A2 Offset Term A2 Offset
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
Min.: -500
Max.: 500
185
H3 Multi-Function Analog Input Settings
H3-oo
Setting
Function LCD Display Description Page
0 Frequency bias Freq Ref Bias 10 V = E1-04 (maximum output frequency) 185
1 Frequency gain Freq Ref Gain
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
of -100 to 0%.
185
2
Auxiliary frequency
reference 1
Aux Reference1
10 V = E1-04 (maximum output frequency)
185
4 Output voltage bias Voltage Bias 10 V = E1-05 (motor rated voltage) 185
7
Overtorque/
undertorque
detection level
Torque Det Level
10 V = Drive rated current (V/f)
185
B PID feedback PID Feedback1 10 V = 100% 185
C PID setpoint PID Set Point 10 V = 100% 185
E
Motor Temperature
(PTC Input)
E Motor PTC 10 V = 100% 185
F Through mode Not Used
Select this setting when using the terminal in a pass-through mode. The terminal
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
185
16
Differential PID
feedback
PID Feedback 2
10 V = 100%
185
1F Through mode Not Used Set this value when using the terminal in the pass-through mode. 185
20
HAND Frequency
Reference
Hand Freq. Ref. Full scale: Max. frequency (E1-04) 185
41 Output Voltage Gain V/f out gain 10 V = 100% 185
B.8 H Parameters: Multi-Function Terminals
342