H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function LCD Display Description Page
1B
During baseblock
(N.C.)
BaseBlk 2
Open: Drive has entered the baseblock state (no output voltage).
1E Restart enabled Dur Flt Restart Closed: An automatic restart is performed
1F
Motor overload alarm
(oL1)
Overload (OL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers
this alarm.
20
Drive overheat pre-
alarm (oH)
OH Prealarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
22
Mechanical weakening
detection
MechFatigue(OL5)
Closed: Mechanical weakening detected.
2F Maintenance period Maintenance
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay
may require maintenance.
30 During torque limit Torque Limit
OLVOLVOLVOLV
Closed: The torque limit has been reached.
37
During frequency
output
During RUN 2
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial
Excitation is being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is
not being performed).
38 Drive enabled Drive Enable
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)
39 Watt hour pulse output Watt-hour Pulse
Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate
the kWh count.
3C
LOCAL/REMOTE
status
Local
Open: REMOTE
Closed: LOCAL
3D During speed search During SpdSrch Closed: Speed Search is being executed.
3E PID feedback low PID Feedback Low Closed: PID feedback level is too low.
3F PID feedback high PID FeedbackHigh Closed: The PID feedback level is too high.
4A During KEB Ride-Thru During KEB Closed: KEB Ride-Thru is being performed.
4C During fast stop During Fast Stop
Closed: A Fast Stop command has been entered from the operator or input
terminals.
4D oH Pre-alarm time limit OH Pre-Alarm Closed: oH pre-alarm time limit has passed.
4E
Braking transistor fault
(rr)
Brk Trans Fault
Closed: The built-in dynamic braking transistor failed.
4F
Braking resistor
overheat (oH)
BrkResistOvHeat
Closed: The dynamic braking resistor has overheated.
50 Waiting to Run Waiting for Run Closed: b1-11 Timer is active.
51 Sequence timer 1 SeqTimer Disable Closed: Sequence timer 1 is active.
52 Sequence timer 2 SeqTimer Cancel Closed: Sequence timer 2 is active.
53 Sequence timer 3 Sequence timer 3 Closed: Sequence timer 3 is active.
54 Sequence timer 4 Sequence Timer 4 Closed: Sequence timer 4 is active.
58 Underload detection UL6 Closed: Underload is detected.
60
Internal cooling fan
alarm
Fan Alrm Det
Closed: Internal cooling fan alarm
71
Secondary PI Feedback
Low
PI2 Feedback Low
Closed: PI2 feedback level is too low.
72
Secondary PI Feedback
High
PI2 FeedbackHigh
Closed: The PI2 feedback level is too high.
80 Pump 2 Control Pump 2 Control
Contactor control for a second pump.
The function is active in contactor multiplex mode only (P1-01 = 1).
81 Pump 3 Control Pump 3 Control
Contactor control for a third pump.
The function is active in contactor multiplex mode only (P1-01 = 1) and when
P3-01 is set to a value greater than 1.
82 Pump 4 Control Pump 4 Control
Contactor control for a fourth pump.
The function is active in contactor multiplex mode only (P1-01 = 1) and when
P3-01 is set to a value greater than 2.
83 Pump 5 Control Pump 5 Control
Contactor control for a fifth pump.
The function is active in contactor multiplex mode only (P1-01 = 1) and when
P3-01 is set to a value greater than 3.
B.7 H Parameters: Multi-Function Terminals
282