10-10
H5-04 Stopping method after communications error 3
H5-05 Communications error detection selection 1
H5-06 Send wait time 5 ms
H5-07 RTS control ON/OFF 1
H5-08 Communications Selection 0
H5-09 CE detection time 2.0 sec
L1-01 Motor protection selection 1
L1-02 Motor protection time constant 1.0 min
L1-03 Alarm operation selection during motor overheating 3
L1-04 Motor overheating operation selection 1
L1-05 Motor temperature input filter time constant 0.20 s
L2-01 Momentary power loss detection 0
L2-02 Momentary power loss ridethru time
0.1 s
*1
L2-03 Min. baseblock time
0.1s
*1
L2-04 Voltage recovery time
0.3 s
*1
L2-05 Undervoltage detection level
190 V
*2
L3-01 Stall prevention selection during acceleration 1
L3-02 Stall prevention level during acceleration 120 %
L3-04 Stall prevention selection during decel 1
L3-05 Stall prevention selection during running 1
L3-06 Stall prevention level during running 120 %
L4-01 Speed agreement detection level 0.0 Hz
L4-02 Speed agreement detection width 2.0 Hz
L4-05 Operation when frequency reference is missing 0
L4-06
F
ref
@ F
ref
Loss
80 %
L5-01 Number of auto restart attempts 0
L5-02 Auto restart operation selection 0
L5-03 Fault Retry Time 10.0 x
L6-01 Torque detection selection 1 0
L6-02 Torque detection level 1 150 %
L6-03 Torque detection time 1 0.1 s
L8-02 Overheat pre-alarm level 95 °C
L8-03 Operation selection after overheat pre-alarm 3
L8-06 Input phase loss detection level 5 %
L8-09 Ground protection selection 1
L8-10 Cooling fan control selection 0
L8-11 Cooling fan control delay time 60 s
L8-12 Ambient temperature 45 °C
L8-15 OL2 characteristics selection at low speeds 1
L8-18 Soft CLA selection 1
L8-19 Frequency reference during OH pre-alarm 20.0 %
N1-01 Hunting-prevention function selection 1
N1-02 Hunting-prevention gain 1.00
N3-01 High-slip braking deceleration frequency width 5 %
N3-02 High-slip braking current limit 150 %
N3-03 High-slip braking stop dwell time 1.0 s
Table 10.1 User Constants
No. Name
Factory
Setting
Setting
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com