 User Constants Settable in Quick Programming Mode
The minimum user constants required for Inverter operation can be monitored and set in quick programming
mode. The user constants displayed in quick programming mode are listed in the following table. These, and
all other user constants, are also displayed in advanced programming mode.
Refer to the overview of modes on page 3-5 for an overview of quick programming mode.
Con-
stant 
Number
Name
Description
Setting 
Range
Factory 
Setting
Change 
during 
Opera-
tion
Control Methods
MEMO-
BUS
 Regis-
ter
Display
V/f
V/f 
with 
PG
Open
-loop 
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
A1-02
Control 
method 
selection
Set the control method for the Inverter.
0: V/f control
1: V/f control with PG
2: Open-loop vector 1 control
3: Flux vector control
4: Open-loop vector 2 control
0 to 4 2 NoQQQQQ102H
Control 
Method
b1-01
Reference 
selection
Set the frequency reference input 
method.
0: Digital Operator
1: Control circuit terminal (analog 
input)
2: MEMOBUS communications
3: Option board
4: Pulse train input
0 to 4 1 NoQQQQQ180H
Reference 
Source
b1-02
Operation 
method 
selection
Set the Run Command input method
0: Digital Operator
1: Control circuit terminal (sequence 
input)
2: MEMOBUS communications
3: Option board
0 to 3 1 NoQQQQQ181H
 Run 
Source
b1-03
Stopping 
method 
selection
Select stopping method when Stop 
Command is sent.
0: Deceleration to stop
1: Coast to stop
2: DC braking stop (Stops faster than 
coast to stop, without regenerative 
operation.)
3: Coast to stop with timer (Run 
Commands are disregarded during 
deceleration time.)
0 to 3 
*10
0 NoQQQQQ182H
Stopping 
Method
C1-01
Accelera-
tion time 1
Set the acceleration time in seconds 
for the output frequency to climb from 
0% to 100%.
0.0 to 
6000.0 
*1
10.0 s
YesQQQQQ200H
Accel 
Time 1
C1-02
Decelera-
tion time 1
Set the deceleration time in seconds 
for the output frequency to fall from 
100% to 0%.
YesQQQQQ201H
 Decel 
Time 1
C6-02
Carrier fre-
quency 
selection
Select carrier wave fixed pattern.
Select F to enable detailed settings 
using constants C6-03 to C6-07.
1 to F
*11
6
*2
NoQQQQ
No
*13
224H
Carrier 
Freq Sel