Adjusting Frequency References
6-33
îš‹ Adjusting Frequency Reference Using Pulse Train Inputs
The frequency reference can be adjusted when b1-01 (Reference Selection) is set to 4 (Pulse Train Input). Set
the pulse frequency in constant H6-02 to 100% reference, and then adjust the gain and bias accordingly using
H6-03 and H6-04.
Related Constants
The following diagram shows the method for adjusting the frequency reference using pulse inputs.
Fig 6.31 Frequency Reference Adjustments Using Pulse Train Inputs
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
H6-01
Pulse train
input function
selection
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2 0 No A A A A A 42CH
Pulse Input Sel
H6-02
Pulse train
input scaling
Set the number of pulses in hertz,
taking the reference to be 100%.
1000
to
32000
1440
Hz
YesAAAAA42DH
PI Scaling
H6-03
Pulse train
input gain
Set the input gain level as a per-
cent when the pulse train set in
H6-02 is input.
0.0 to
1000.0
100.0
%
Yes A A A A A 42EH
Pulse Input
Gain
H6-04
Pulse train
input bias
Set the input bias when the pulse
train is 0.
-100.0
to
100.0
0.0% Yes A A A A A 42FH
Pulse Input
Bias
H6-05
Pulse train
input filter time
Set the pulse train input primary
delay filter time constant in sec-
onds.
0.00 to
2.00
0.10
s
YesAAAAA430H
PI Filter Time
RP
Cycle
measurement
Filter
H6
-
05
H6
-
01
Master speed
frequency
PID feedback
PID target value
=0
=2
=1
Scaling using H6-02
Gain and bias
Pulse
1
1+sT
0
H6
-
04
H6
-
03
100

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals