10-22
Using Braking Units in Parallel
This example shows wiring for using two Braking Units in parallel.
There are connectors for selecting whether each Braking Unit is to be a Master or Slave. Select “Master” for
the first Braking Unit only, and select “Slave” for all other Braking Units (i.e., from the second Unit onwards).
Fig 10.11
A sequence is required to turn OFF the
power supply for the thermal overload relay
trip contacts of the Braking Resistor Unit.
MCCB
Inverter
Motor
Ground to 100 max.
Forward Run Com-
mand (forward run
when ON)
Reverse Run Com-
mand (reverse run
when ON)
Forward Run/Stop
Reverse Run/Stop
Braking Unit
External fault
Fault contacts
3-phase power
200 to 220 V 50 Hz
200 to 230 V 60 Hz
Thermal
protector
Thermal
protector
Brak-
ing
Resis-
tor Unit
Brak-
ing
Resis-
tor Unit
Thermal switch
Level
detector
Braking Unit 2
Thermal switch
Cooling fan
Overload relay trip contact
of Braking Resistor Unit
Fault contact output
* Disable stall prevention during deceleration by setting L3-04 to Resistor Unit. The motor may
not stop within the deceleration time if this setting is not changed.
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals