EasyManua.ls Logo

YASKAWA Varispeed G7 - H: Terminal Function Constants

YASKAWA Varispeed G7
499 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-46
H: Terminal Function Constants
The following settings are made with the terminal function constants (H constants): Settings for external ter-
minal functions.
Multi-function Contact Inputs: H1
User constants for multi-function contact inputs are shown in the following tables.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H1-01
Terminal S3
function selec-
tion
Multi-function contact input
1
0 to 79 24 No A A A A A 400H -
Terminal S3
Sel
H1-02
Terminal S4
function selec-
tion
Multi-function contact input
2
0 to 79 14 No A A A A A 401H -
Terminal S4
Sel
H1-03
Terminal S5
function selec-
tion
Multi-function contact input
3
0 to 79
3 (0)
*
No A A A A A 402H -
Terminal S5
Sel
H1-04
Terminal S6
function selec-
tion
Multi-function contact input
4
0 to 79
4 (3)
*
No A A A A A 403H -
Terminal S6
Sel
H1-05
Terminal S7
function selec-
tion
Multi-function contact input
5
0 to 79
6 (4)
*
No A A A A A 404H -
Terminal S7
Sel
H1-06
Terminal S8
function selec-
tion
Multi-function contact input
6
0 to 79
8 (6)
*
No A A A A A 405H -
Terminal S8
Sel
H1-07
Terminal S9
function selec-
tion
Multi-function contact input
7
0 to 79 5 No A A A A A 406H -
Terminal S9
Sel
H1-08
Terminal S10
function selec-
tion
Multi-function contact input
8
0 to 79 32 No A A A A A 407H -
Terminal S10
Sel

Table of Contents