Digital Operator Functions
6-151
îš‹ Copying Constants
The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).
• Store Inverter constant set values in the Digital Operator (READ)
• Write constant set values stored in the Digital Operator to the Inverter (COPY)
• Compare constant set values stored in the Digital Operator with Inverter constants (VERIFY)
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
o3-01
Copy function
selection
0: Normal operation
1: READ (Inverter to Operator)
2: COPY (Operator to Inverter)
3: Verify (compare)
0 to 3 0 No A A A A A 515H
Copy Function
Sel
o3-02
Read permitted
selection
0: Read prohibited
1: Read permitted
0 or 1 0 No A A A A A 516H
Copy Allow-
able

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals