3-10
Advanced Programming Mode
In advanced programming mode, all Inverter constants can be monitored and set.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to
change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
Refer to Chapter 5 User Constants for details on the constants.
Example Operations
Key operations in advanced programming mode are shown in the following figure.
Fig 3.6 Operations in Advanced Programming Mode
A1- 00= 0
** Main Menu **
-DRIVE-
Operation
** Main Menu **
-QUICK-
Quick Setting
** Main Menu **
-ADV-
Programming
** Main Menu **
-VERIFY-
Modified Consts
** Main Menu **
-A.TUNE-
Auto-Tuning
MENU
Initialization
-ADV-
A1-00=1
Select Language
MENU
MENU
MENU
MENU
ESC
DATA
ENTER
Select Language
-ADV-
A1- 00 =0
English
ESC
-ADV-
Select Language
English
*1*
ESC
DATA
ENTER
RESET
Monitor Display Setting DisplayMode Selection Display
PID Control
-ADV-
b5-01=0
PID Mode
ESC
ESC
DATA
ENTER
RESET
Control Method
-ADV-
A1- 02 =2
Open Loop Vector
PID Mode
-ADV-
b5- 01 =0
Disabled
Control Method
-ADV-
A1- 02= 2
Open Loop Vector
ESC
DATA
ENTER
*2*
*1*
*2*
1 2
1 2
PID Mode
-ADV-
b5-01= 0
Disabled
*0*
*0*
Fb los Det Time
-ADV-
(0.0025.5)
1.0Sec
b5- 14= 1.0Sec
Fb los Det Time
-ADV-
(0.0025.5)
1.0Sec
b5-14=01.0Sec
ESC
DATA
ENTER
3 4
3 4
Torque Limit
-ADV-
L7-01=200%
Torque Limit Fwd
ESC
ESC
DATA
ENTER
RESET
ESC
DATA
ENTER
5 6
5 6
Torque Limit Fwd
-ADV-
(0300)
200%
L7- 01= 200%
Torque Limit Fwd
-ADV-
(0300)
200%
L7-01= 2 00%
Torq Lmt Rev RgnTorq Lmt Rev Rgn
Torq Lmt Rev Rgn
-ADV-
(0300)
200%
L7-04= 2 00%
-ADV-
(0300)
200%
L7- 04= 200%
A B
A B
Initialization
-ADV-
A1-02 =2
Control Method
ESC
RESET
PID Control
-ADV-
b5 - 14= 1.0Sec
Fb los Det Time
ESC
RESET
-ADV-
L7- 04= 200%
Torque Limit
ESC
RESET

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals