Adjusting Frequency References
6-31
When constant H3-09 or H3-05 is set to D (frequency bias 2), the frequency equivalent to the terminal A2 or
A3 input voltage is added to A1 as a bias.
îš‹ Operation Avoiding Resonance (Jump Frequency Function)
The jump frequency function operates the motor while avoiding resonance caused by characteristic frequen-
cies in the machinery.
This function is effective in creating a frequency reference dead band.
During constant-speed operation, operation within the jump frequency range is prohibited. Smooth operation
still used during acceleration and deceleration, i.e., jumps are not performed.
Related Constants
The relationship between the output frequency and the jump frequency reference is as follows:
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
d3-01
Jump fre-
quency 1
Set the center values of the jump
frequencies in Hz.
This function is disabled by set-
ting the jump frequency to 0 Hz.
Always ensure that the following
applies:
d3-01 ≥ d3-02 ≥ d3-03
Operation in the jump frequency
range is prohibited but during
acceleration and deceleration,
speed changes smoothly without
jump.
0.0 to
400.0
0.0 Hz No A A A A A 294H
Jump Freq 1
d3-02
Jump fre-
quency 2
0.0 Hz No A A A A A 295H
Jump Freq 2
d3-03
Jump fre-
quency 3
0.0 Hz No A A A A A 296H
Jump Freq 3
d3-04
Jump fre-
quency width
Sets the jump frequency band-
width in Hz.
The jump frequency will be the
jump frequency ± d3-04.
0.0 to
20.0
1.0 Hz No A A A A A 297H
Jump Band-
width
Terminal A1 input voltage
Frequency reference
H3-02
10%
Bias
0 V 10 V