Improved Operating Efficiency
6-41
 Stabilizing Speed (Speed Feedback Detection Function)
The speed feedback detection control (AFR) function measures the stability of the speed when a load is sud-
denly applied, by calculating the amount of fluctuation of the torque current feedback value, and compensat-
ing the output frequency with the amount of fluctuation.
Related Constants
Con-
stant 
Number
Name
Description
Setting 
Range
Factory 
Setting
Change 
during 
Opera-
tion
Control Methods
MEMO
BUS
 Regis-
ter
Display
V/f
V/f 
with 
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
N2-01
Speed feed-
back detection 
control (AFR) 
gain
Set the internal speed feedback 
detection control gain using the 
multiplication function.
Normally, there is no need to 
make this setting.
Adjust this constant as follows:
• If hunting occurs, increase the 
set value.
• If response is low, decrease the 
set value.
Adjust the setting by 0.05 at a 
time, while checking the 
response.
0.00 to 
10.00
1.00 No No No A No No 584H
AFR Gain
N2-02
Speed feed-
back detection 
control (AFR) 
time constant
Set the time constant to decide the 
rate of change in the speed feed-
back detection control.
0 to 
2000
50 ms No No No A No No 585H
AFR Time
N2-03
Speed feed-
back detection 
control (AFR) 
time constant 2
Increase the setting if overvoltage 
(OV) failures occur at the comple-
tion of acceleration or when the 
load changes radically.
0 to 
2000
750 
ms
No No No A No No 586H
AFR Time 2