User Constant Tables
5-73
Feed Forward: N5
User constants for the feed forward control are shown in the following table.
* 1. When the control method is changed, the factory setting will change. The flux vector factory setting is given.
* 2. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
 o: Digital Operator Constants
The following settings are made with the Digital Operator constants (o constants): Multi-function selections
and the copy function.
Monitor Select: o1
User constants for Digital Operator Displays are shown in the following table.
Con-
stant 
Number
Name
Description
Setting 
Range
Factory 
Setting
Change 
during 
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f 
V/f 
with 
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
N5-01
Feed forward 
control selec-
tion
Select the feed forward con-
trol.
0: Disabled
1: Enabled
0 or 1
0
*1
No No No No A A 5B0H
4-21
6-142
Feedfoward 
Sel
N5-02
Motor accel-
eration time
Set the time required to 
accelerate the motor at the 
rated torque (T
100
) to the 
rated speed (Nr).
J: GD
2
/4, P: Motor rated out-
put
However, 
0.001 
to 
10.000
0.178 s
*2
No No No No A A 5B1H
4-21
6-142
Motor Accel 
Time
N5-03
Feed forward 
proportional 
gain
Set the proportional gain for 
feed forward control.
Speed reference response will 
increase as the setting of N5-
03 is increased.
0.00 to 
100.00
1.0 No No No No A A 5B2H
4-21
6-142
Feedfoward 
Gain
Con-
stant 
Number
Name
Description
Setting 
Range
Factory 
Setting
Change 
during 
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f 
V/f 
with 
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
o1-01
Monitor 
selection
Set the number of the monitor 
item to be displayed in the 
earliest 4 monitor items. (U1-
)
The output monitor voltage 
(factory setting) can be 
changed.
4 to 45
6 Yes A A A A A 500H -
User Monitor 
Sel
4 to 99
2π x J [kgm
2
] x Nr [min
-1
]
ta = 
60 
x T
100
 [N x m]
[s] 
T
100
 = 
× 10
3 
[N x m]
60
2π
x
P [kW]
Nr [min
-1
]