User Constant Tables
5-45
Communications Option Boards: F6
User constants for a Communications Option Board are shown in the following table.
* Applicable for G7-Series Inverters with software versions PRG: 1038 or later.
Refer to MECHATROLINK COMMUNICATIONS INTERFACE CARD INSTRUCTIONS (TOBPC73060008) for details.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F6-01
Operation
selection after
communica-
tions error
Set the stopping method for
communications errors.
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 1 No A A A A A 3A2H -
BUS Fault
Sel
F6-02
Input level of
external fault
from Com-
munications
Option Board
0: Always detect
1: Detect during operation
0 or 1 0 No A A A A A 3A3H -
EF0 Detec-
tion
F6-03
Stopping
method for
external fault
from Com-
munications
Option Board
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 1 No A A A A A 3A4H -
EF0 Fault
Action
F6-04
Trace sam-
pling from
Communica-
tions Option
Board
-
0 to
60000
0 No A A A A A 3A5H -
Trace Sam-
ple Tim
F6-06
Torque refer-
ence/torque
limit selec-
tion from
optical option
0: Torque reference/torque
limit from transmission
disabled.
1: Torque reference/torque
limit from transmission
enabled.
0 or 1 0 No No No No A A 3A7H -
Torq Ref/Lmt
Sel
F6-08
∗
Operation
selection after
SI-T WDT
error
Set the stopping method for
SI-T WDT errors (E5).
0: Deceleration stop using
deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using
deceleration time in C1-
09
3: Continue operation
0 to 3 1 No A A A A A 3B6H -
SI-T
WDTErr Sel
F6-09
∗
Number of
SI-T BUS
error detec-
tion
Set the number which SI-T
detects BUS errors.
2 to 10 2 No A A A A A 3B7H -
SI-T BUS
DET Ctr

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals