5-44
Digital Output Boards (DO-02C and DO-08): F5
User constants for the Digital Output Board are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
F5-01
Channel 1
output selec-
tion
Effective when a Digital Out-
put Board (DO-02C or DO-
08) is used.
Set the number of the multi-
function output to be output.
0 to 37 0 No A A A A A 399H
6-162
DO Ch1
Select
F5-02
Channel 2
output selec-
tion
Effective when a Digital Out-
put Board (DO-02C or DO-
08) is used.
Set the number of the multi-
function output to be output.
0 to 37 1 No A A A A A 39AH
6-162
DO Ch2
Select
F5-03
Channel 3
output selec-
tion
Effective when a DO-08 Dig-
ital Output Board is used.
Set the number of the multi-
function output to be output.
0 to 37 2 No A A A A A 39BH
6-162
DO Ch3
Select
F5-04
Channel 4
output selec-
tion
Effective when a DO-08 Dig-
ital Output Board is used.
Set the number of the multi-
function output to be output.
0 to 37 4 No A A A A A 39CH
6-162
DO Ch4
Select
F5-05
Channel 5
output selec-
tion
Effective when a DO-08 Dig-
ital Output Board is used.
Set the number of the multi-
function output to be output.
0 to 37 6 No A A A A A 39DH
6-162
DO Ch5
Select
F5-06
Channel 6
output selec-
tion
Effective when a DO-08 Dig-
ital Output Board is used.
Set the number of the multi-
function output to be output.
0 to 37 37 No A A A A A 39EH
6-162
DO Ch6
Select
F5-07
Channel 7
output selec-
tion
Effective when a DO-08 Dig-
ital Output Board is used.
Set the number of the multi-
function output to be output.
0 to 37 0F No A A A A A 39FH
6-163
DO Ch7
Select
F5-08
Channel 8
output selec-
tion
Effective when a DO-08 Dig-
ital Output Board is used.
Set the number of the multi-
function output to be output.
0 to 37 0F No A A A A A 3A0H
6-163
DO Ch8
Select
F5-09
DO-08 out-
put mode
selection
Effective when a DO-08 Dig-
ital Output Board is used.
Set the output mode.
0: 8-channel individual out-
puts
1: Binary code output
2: Output according to
F5-01 to F5-08 settings.
0 to 2 0 No A A A A A 3A1H
6-163
DO-08 Selec-
tion

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals