User Constant Tables
5-47
* The factory settings in the parentheses are for 3-wire sequence.
Multi-function Contact Input Functions
H1-09
Terminal S11
function selec-
tion
Multi-function contact input
9
0 to 79 7 No A A A A A 408H -
Terminal S11
Sel
H1-10
Terminal S12
function selec-
tion
Multi-function contact input
10
0 to 79 15 No A A A A A 409H -
Terminal S12
Sel
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
0 3-wire sequence (Forward/Reverse Run Command) Yes Yes Yes Yes Yes 6-11
1 Local/Remote selection (ON: Local, OFF: Remote) Yes Yes Yes Yes Yes 6-76
2 Option/Inverter selection (ON: Option board) Yes Yes Yes Yes Yes
6-83
6-164
3
Multi-step speed reference 1
When H3-05 is set to 0, this function is combined with the master/auxiliary speed
switch.
Yes Yes Ye s Ye s Yes 6-5
4 Multi-step speed reference 2 Yes Yes Yes Yes Yes 6-5
5 Multi-step speed reference 3 Yes Yes Yes Yes Yes 6-5
6 Jog frequency command (higher priority than multi-step speed reference) Yes Yes Yes Yes Yes 6-5
7 Accel/decel time 1 Yes Yes Yes Yes Yes 6-19
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes Yes Yes 6-77
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes Yes Yes 6-77
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, fre-
quency on hold)
Yes Yes Ye s Ye s Yes 6 -7 8
B OH2 alarm signal input (ON: OH2 will be displayed) Yes Yes Yes Yes Yes -
C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes Yes -
D
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f con-
trol)
NoYesNoNoNo6-137
E Speed control integral reset (ON: Integral control disabled) No Yes No Yes Yes 6-137
FNot used (Set when a terminal is not used) ----- -
10 Up command (Always set with the down command) Yes Yes Yes Yes Yes 6-79
11 Down command (Always set with the up command) Yes Yes Yes Yes Yes 6-79
12 FJOG command (ON: Forward run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
13 RJOG command (ON: Reverse run at jog frequency d1-17) Yes Yes Yes Yes Yes 6-84
14 Fault reset (Reset when turned ON) Yes Yes Yes Yes Yes 7-2
15
Emergency stop. (Normally open condition: Deceleration to stop in deceleration
time set in C1-09 when ON.)
Yes Yes Ye s Ye s Yes 6 -1 7
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals