5-52
H3-05
Multi-func-
tion analog
input (termi-
nal A3) func-
tion selection
Select multi-function analog
input function for terminal
A3. Refer to the next page.
0 to 1F 2 No A A A A A 414H
6-28
6-128
Terminal A3
Sel
H3-06
Gain (termi-
nal A3)
Sets the input gain (level)
when 10 V is input.
Set according to the 100%
value selected from H3-05.
0.0 to
1000.0
100.0% Yes A A A A A 415H
6-28
6-128
Terminal A3
Gain
H3-07
Bias (termi-
nal A3)
Sets the input gain (level)
when 0 V is input.
Set according to the 100%
value selected from H3-05.
-100.0
to
+100.0
0.0% Yes A A A A A 416H
6-28
6-128
Terminal A3
Bias
H3-08
Signal level
selection
(terminal A2)
0: 0 to 10V
1: -10V to 10V
2: 4 to 20 mA (9-bit input).
Switch current and voltage
input using the switch on the
control panel.
0 to 2 2 No A A A A A 417H
6-28
6-128
Term A2 Sig-
nal
H3-09
Multi-func-
tion analog
input (termi-
nal A2) func-
tion selection
Select multi-function analog
input function for terminal
A2. Refer to the next table.
0 to 1F 0 No A A A A A 418H
6-29
6-128
Terminal A2
Sel
H3-10
Gain
(terminal A2)
Sets the input gain (level)
when 10 V (20 mA) is input.
Set according to the 100%
value for the function set for
H3-09.
0.0 to
1000.0
100.0% Yes A A A A A 419H
6-29
6-129
Terminal A2
Gain
H3-11
Bias
(terminal A2)
Sets the input gain (level)
when 0 V (4 mA) is input.
Set according to the 100%
value for the function set for
H3-09.
-100.0
to
+100.0
0.0% Yes A A A A A 41AH
6-29
6-129
Terminal A2
Bias
H3-12
Analog input
filter time
constant
Sets primary delay filter time
constant in seconds for the
analog input terminal.
Effective for noise control
etc.
0.00 to
2.00
0.03
s
No A A A A A 41BH 6-29
Filter Avg
Time
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2