EasyManua.ls Logo

YASKAWA Varispeed G7 - Page 395

YASKAWA Varispeed G7
499 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Protective and Diagnostic Functions
7-5
FAN
Cooling
Fan Fault
Inverter’s Cooling Fan Fault
An Inverters cooling fan fault was
detected, and the Inverter-overload
protection was activated based on the
internal electric thermal value.
This fault is detected when L8-32 is
set to 0.
The Inverter continued running with
an overload after the cooling fan
stopped.
Replace the cooling fan. (Contact
our sales representative.)
OH3
Motor
Overheat 1
Motor Overheating Alarm
The Inverter will stop or will continue
to operate according to the setting of
L1-03.
The motor has overheated.
Check the size of the load and the
length of the acceleration, deceler-
ation, and cycle times.
Check the V/f characteristics.
Check the Motor Rated Current
(E2-01).
OH4
Motor
Overheat 2
Motor Overheating Fault
The Inverter will stop according to the
setting of L1-04.
The motor has overheated.
Check the size of the load and the
length of the acceleration, deceler-
ation, and cycle times.
Check the V/f characteristics.
Check the Motor Rated Current
(E2-01).
RH
DynBrk
Resistor
Installed Braking Resistor Over-
heating
Braking resistor protection function
set in L8-01 has operated.
The deceleration time is too short and
the regenerative energy from the
motor is too large.
Reduce the load, increase the
deceleration time, or reduce the
motor speed.
Change to a Braking Resistor
Unit.
RR
DynBrk
Transistr
Internal Braking Transistor Fault
The braking transistor is not operating
properly.
The braking transistor is damaged.
The Inverters control circuits are
faulty.
Try turning the power supply
off and on.
Replace the Inverter if the fault
continues to occur.
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions