7-12
CPF23
Option
DPRAM
Err
Communications Option Board
DPRAM Error
Communications Option Board fault. Replace the option board.
The copy function of the Digital Oper-
ator was used during communications.
• Use the copy function off-line.
• Use the copy function with an
option board removed.
The option board is not connected
properly.
Turn off the power and insert the
board again.
VCF
Vcn Fail-
ure
Main Circuit Capacitor Neutral
Point Potential Error
An excessive imbalance occurred in
the main circuit capacitor’s neutral
point potential.
A loss in capacity due to aging of the
main circuit capacitor.
Replace the main circuit capacitor.
(Consult your YASKAWA repre-
sentative.)
The Inverter parts are faulty. Replace the Inverter.
An open phase was detected for an
output.
Refer to LF (output open phase) in
this table.
Carrier frequency set value (C6-03,
C6-04) is unsuitable.
Check the set values for C6-03
and C6-04. The maximum output
frequency that can be set for 400
V Class Inverters is restricted by
the carrier frequency setting.
Refer to page 6-45.
In V/f or open-loop vector control, the
motor consecutively loses synchro-
nism (the output current exceeds
200% of the Inverter rated current).
• Reduce the load.
• Increase the acceleration time.
• Check the settings for V/f con-
trol.
• Use larger capacity Inverter.
OPERA-
TOR ERR
RAM
CHECK
ERR
Operator Error (Internal RAM
Fault)
At power ON, an error was detected
from the results of the internal RAM
Write/Read check.
---
Replace the Operator.
OPERA-
TOR ERR
ROM
CHECK
ERR
Operator Error (CPU Internal ROM
Fault)
At power ON and during operation, an
error was detected when the internal
ROM was checked.
OPERA-
TOR ERR
DATA
SEND
ERR
Operator Error (Transmission Cir-
cuit Fault)
During operation, send processing did
not complete within 500 ms continu-
ously at least 10 times.
OPERA-
TOR ERR
RAM
CHECK
ERR
Operator Error (Internal RAM
Fault)
During operation, an error was
detected when the display pattern for
the character code 80 to 8F recorded
in the internal RAM was checked.
OPERA-
TOR ERR
WAT CH -
DOG ERR
Operator Error (Watchdog Error)
During operation, an error was
detected in the program execution.
Table 7.1 Fault Displays and Processing (Continued)
Display Meaning Probable Causes Corrective Actions

Table of Contents

Other manuals for YASKAWA Varispeed G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed G7 and is the answer not in the manual?

YASKAWA Varispeed G7 Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed G7
CategoryInverter
LanguageEnglish

Related product manuals