10-34
Table 10.7 User Constants (Continued)
H4-01 Monitor selection (terminal FM) 2
H4-02 Gain (terminal FM) 1.00
H4-03 Bias (terminal FM) 0.0
H4-04 Monitor selection (terminal AM) 3
H4-05 Gain (terminal AM) 0.50
H4-06 Bias (terminal AM) 0.0
H4-07
Analog output 1 signal level selec-
tion
0
H4-08
Analog output 2 signal level selec-
tion
0
H5-01 Slave address 1F
H5-02 Communication speed selection 3
H5-03 Communication parity selection 0
H5-04
Stopping method after communi-
cation error
3
H5-05
Communication error detection
selection
1
H5-06 Send wait time 5
H5-07 RTS control ON/OFF 1
H5-10
*18
Unit Selection for MEMOBUS
Register 0025H
0
H6-01 Pulse train input function selection 0
H6-02 Pulse train input scaling 1440
H6-03 Pulse train input gain 100.0
H6-04 Pulse train input bias 0.0
H6-05 Pulse train input filter time 0.10
H6-06 Pulse train monitor selection 2
H6-07 Pulse train monitor scaling 1440
L1-01 Motor protection selection 1
L1-02 Motor protection time constant 1.0
No. Name
Fac-
tory
Setting
Set-
ting
L1-03
Alarm operation selection during
motor overheating
3
L1-04
Motor overheating operation selec-
tion
1
L1-05
Motor temperature input filter time
constant
0.20
L2-01 Momentary power loss detection 0
L2-02
Momentary power loss ridethru
time
0.1
*6
L2-03 Min. baseblock time
0.2
*6
L2-04 Voltage recovery time
0.3
*6
L2-05 Undervoltage detection level
190
*9
L2-06 KEB deceleration time 0.0
L2-07 Momentary recovery time
0
*15
L2-08
Frequency reduction gain at KEB
start
100
L3-01
Stall prevention selection during
accel
1
L3-02 Stall prevention level during accel 150
L3-03 Stall prevention limit during accel 50
L3-04
Stall prevention selection during
decel
1
L3-05
Stall prevention selection during
running
1
L3-06
Stall prevention level during run-
ning
160
L3-11 Overvoltage inhibit selection 0
L3-12 Overvoltage inhibit voltage level
380
*9
L4-01 Speed agreement detection level 0.0
L4-02 Speed agreement detection width 2.0
L4-03
Speed agreement detection level
(+/-)
0.0
L4-04
Speed agreement detection width
(+/-)
2.0
L4-05
Operation when frequency refer-
ence is missing
0
L5-01 Number of auto restart attempts 0
No. Name
Fac-
tory
Setting
Set-
ting

Table of Contents