Installation
142
Aastra 415/430 as of R3.2
syd-0344/1.6 – R3.2 – 09.2014
Tab. 68 Connection in slot IC1 (Aastra 415) or slot IC1, 2 or 3 (Aastra 430)
Tab. 69 Connections of control inputs and outputs
Freely connectable relay contacts
The two freely connectable relay contacts can be used to control external devices
or equipment such as heating, alarm or outdoor lighting systems (possibly via ex-
ternal relay for 230VAC).
There are no special requirements for the cables.
Tab. 70 Relay operating data
RJ45
Communication
server
RJ45
Communication
server
Socket X1 Pin Signal Socket X3 Pin Signal
1– 1–
2– 2–
3 O1-1 3 –
4 O2-1 4 –
5 O2-2 5 –
6 O1-2 6 –
7– 7–
8– 8–
Socket X2 Pin Signal Socket X4 Pin Signal
1– 1–
2– 2–
3I3-1 3 –
4I4-1 4 –
5I4-2 5 –
6I3-2 6 –
7– 7–
8– 8–
IO port Signal Function
1 O1-1, O1-2 Floating contact, relay 1
2 O2-1, O2-2 Floating contact, relay 2
3 I3-1, I3-2 Control input 1
4 I4-1, I4-2 Control input 2
Parameter Value
Number of changeover switches per relay 1
Insulation between the changeover
switches
0.5 kV
Type of contact no (normally open, NO contact, make contact)
max. contact loading 24 VDC, 30 VAC, 1 A