2600T Series Pressure transmitters | OI/266/PB-EN Rev. E 59
Appendix A – Device mapping
Idx Parameter Data Type Size Storage Class Range / Selection Note
n+24 IDENT_NUMBER_SELECT RW S U8 1 S
0: 0x09700 profile specific one AI
1: 0x3450 Device specific 2600T-266
2: 0x009B 600T_EN Profile 2.0
3: 0x09760 profile specific MultiVariable
127: Adaptation Adaptation Mode
128: 0x09701 profile specific two AIs
129: 0x09702 profile specific three AIs
130: 0x09653 AFK800
131: 0x052B 2600T-264
0x04C2 2000T / 2600T-265
n+25 HW_WRITE_PROTECTION R S U8 1 D
0: Unprotected (default)
Reflects the Push Button position
1: Protected
n+26 FEATURE R R DS-68 8 N
Supported 0-0-0-3 (hex)
Condensed Status
Condensed and Classic Status/Diagnostic both
supported
Classic Status
Enabled
0-0-0-1 (hex) Condensed enabled
0-0-0-2 (hex) Classic enabled
n+27 COND_STATUS_DIAG RW S U8 1 S
0: Select Classic Status/Diagnostic
Default = Condensed Status/Diagnostic Enabled
1: Select Condensed Status/Diagnostic
n+28 DIAG_EVENT_SWITCH RW R Diag-switch 50 S
0x34,0x34,0x34,0x00,0x36,0x36,0x36,0x00,x00,0x00,0x57,0x57,0x0
0,0x00,0x00,0x00,0x34,0x34,0x02,0x00,0x01,0x00,0x00,0x34,0x02,
0x00,0x00,0x00,0x00,0x00,0x57,0x01,0x34,0x00,0x00,0x00,0x00,0x
00,0x01,0x01,0x00,0x00,0x02,0x00,0x00,0x00,0x00,0x00,0x00,0x00
29-32 NULL_ // reserved by PNO
MANUFACTURER SPECIFIC PARAMETERS
Idx Parameter Data Type Size Storage Class Range / Selection Note
n+33 CB_FW_REVISION R S V_STR 8 Cst Electronics Software Revision xx.yy.zz
n+34 CB_HW_REVISION R S V_STR 8 Cst Electronics Hardware Revision xx.yy.zz
n+35 FE_FW_REV R S V_STR 8 Cst Sensor Software Revision xx.yy.zz
n+36 FE_HW_REV R S V_STR 8 Cst Sensor Hardware Revision xx.yy.zz
n+37 DIAGNOSIS_WORST_COND R S U16 2 D cc.gggggg.dddddddd
n+38 DIAGNOSIS_EXT_HISTORY R S O_STR 6 D
Permanent copy of DIAGNOSIS_EXT (idx n+14). Error
conditions becoming active in the DIAGNOSIS_EXT
remain set in this parameter for Historical analysis
Only authorized personnel can reset this parameter
n+39 DIAGNOSIS_CONDITION_DETAILS_IDX RW S U8 1 N The writing of an Error code enables the firmware to update the DIAGNOSIS_DETAILS (idx n+ 40) with details
n+40 DIAGNOSIS_DETAILS
COUNTER R S U16 2 D
After the idx n+39 has been written with an error code,
all their details are returned when this parameter is read.
Number of times the error is occurred during the device’s
life
TIME_COUNTER R S TIME_DIFF 6 D ddd/hh/mm/ss (days, hours, minutes, seconds) Period of time the error has been active
LAST_TIME R S DATE_S 6 D ddd/hh/mm/ss (days, hours, minutes, seconds) Time elapsed from last error activation
ROOT_CAUSE_LIST R S O_STR 8 D
Up to 8 details (codes) for each error condition. See
Appendix B for the Diagnostic Table
All the active detailed root causes errors relating the err.
condition code written in the idx n+39

Table of Contents

Other manuals for ABB 2600T Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB 2600T Series and is the answer not in the manual?

ABB 2600T Series Specifications

General IconGeneral
BrandABB
Model2600T Series
CategoryTransmitter
LanguageEnglish

Related product manuals