Use in explosion-proof areas
16 265Dx, 265VS IM/265D/V-EN-02
Pos: 7.8 /Überschr iften/1.1/1-spal tig/D - F/Einsatz in Ber eichen mit brennbarem Staub @ 1\ mod_1147685206593_3101. doc @ 11189
2.3 Use in areas with combustible dust
Pos: 7.9 /Ex-tec hnische Sicherheits hinweise/Druck/ Druckmessumformer/A llgemein/Einsatz i n Bereichen mit brennbarem St aub @ 3\mod_1157963371984_31 01.doc @ 41029
Installation must be performed in accordance with EN 50281-1-2.
• Transmitters can only be connected using cable glands certified in accordance with Directive
94/9/EC (ATEX) (not included in scope of delivery). The cable gland must also conform to IP
67 type of protection. Allowing for self-heating, the smoldering temperature of the dust must
be at least 85 K higher than the ambient temperature.
Caution - Risk
When using separating sensors with an anti-stick coating, be aware of the risk of electrostatic
discharge (with consideration given to the medium and transport speed).
Pos: 7.10 /Übersc hriften/1.1/1-spal tig/J - L/Kategori e 3 für den Einsatz in Zone 2 @ 3\mod_1157964 061000_3101.doc @ 41113
2.4 Category 3 for use in "Zone 2"
Pos: 7.11 /Ex-tec hnische Sicherheits hinweise/Druck/ Druckmessumformer/Al lgemein/Kategori e 3 für den Einsatz in Zone 2 @ 3\mod_1157 963321781_3101.doc @ 41008
• The transmitter must be connected using a certified cable gland (not included in scope of
delivery). The cable gland must satisfy the requirements of explosion protection type
"Increased safety EEx e" in accordance with Directive 94/9/EC (ATEX). Additionally, the
conditions stipulated in the type-examination certificate for the cable gland must be
observed.
Warning - Risk
Opening the housing during operation (with the operating voltage switched on) is not
permitted.
Opening the cover presents a risk of spark formation and, therefore, explosion.