8.6.1 Parameter description
Pos: 19.25 /Konfi guration, Parametr ierung/Druck/Dr uckmessumformer/Druck messumformer 265Dx, 265Vx /Parameterbesc hreibung @ 5\mod_1164102970328_310 1.doc @ 49035
8.6.1.1 "VIEW" parameter
Temporary display of display values 1 to 9 (setting is volatile)
The following measured values can be set:
Output signal in physical unit
265Dx: Current measured value for differential pressure, or variable derived from this, such
as flowrate / level, with customized unit in each case
265Vx: Current measured value for absolute pressure; corresponds to "OUT" with
PROFIBUS PA
Setting changes under "OUT 0 %" and "OUT 100 %"; desired unit under "UNIT_OUT"
Percentage value of output signal
Output current (not with fieldbus transmitters)
• Static pressure
• Pressure/differential pressure
Current pressure/differential pressure value in range between lower and upper range limit
values set
Setting changes under "GET 0 % / 100 %" or "SET 0 % / 100 %"; desired unit under
"UNIT_p/dp"
• Sensor temperature
8.6.1.2 "GET 0 %" and "GET 100 %" parameters
Setting with applied pressure
8.6.1.3 "SET 0 %" and "SET 100 %" parameters
Setting without applied pressure
8.6.1.4 "SHIFT ZERO" parameter
Zero correction (e.g. oblique sensor)
8.6.1.5 "SHIFT OFFSET" parameter
Offset shift (parallel shift; see also "Configuration")
8.6.1.6 "OUT 0 %" and "OUT 100 %" parameters
Setting for output variables (including "VIEW", display code no.1, and "DISPLAY", display code
no. 1)