Configuration
50 265Dx, 265VS IM/265D/V-EN-02
Pos: 19.11 /Übers chriften/1.1/1-s paltig/J - L/Konfigur ation mit dem LCD-Anzeiger @ 2\mod_1156319408468_3101. doc @ 39224
8.4 Configuration with the LCD display
Pos: 19.12 /Konfi guration, Parametr ierung/Druck/Dr uckmessumformer/Druck messumformer 265G, 265A/Konf iguration mit dem LCD-Anzeiger @ 17\mod_120109785 9906_3101.doc @ 153893
The LCD display can be used to configure the transmitter by means of the (-/+/M) buttons, as
follows:
Warning - Potential damage to parts
Operating the control buttons with a magnetic screwdriver is not permitted.
Important
The information in parentheses refers to the relevant menu item. The menu items are
displayed in the 1st and 2nd lines of the LCD display. The full menu structure can be found in
the section "Menu structure".
(EXIT) Exit the menu
(VIEW) View selected measured values and calculation values
(GET 0 %) Lower range value with applied pressure
(GET 100 %) Upper range value with applied pressure
(SET 0 %) Lower range value without applied pressure
(SET 100 %) Upper range value without applied pressure
(SHIFTZERO) Correct zero drift (e.g., oblique sensor)
(OFFSET SHIFT) Parallel shift
(OUT 0 %) Scaling of output variable start value
(OUT 100 %) Scaling of output variable end value
• (DAMPING) Damping
(ALARM CURRENT) Output current in the event of an error; only available for 4 … 20 mA
devices with HART protocol
(DISPLAY) Display value
(UNIT) "p" and "OUT" units
• (FUNCTION) Characteristic
(ADDRESS) Fieldbus address; only available for devices with PROFIBUS PA or
FOUNDATION Fieldbus protocol
The sections that follow contain explanations for some of the menu items listed above.