5.8 Connecting cable
Pos: 13.24 /Elekt rischer Anschluss/ Druck/Druckmessumfor mer/Allgemein/Ansc hlusskabel @ 3\mod_115761 6660609_3101.doc @ 39583
Communication between the transmitter and PC or laptop is only possible if the cabling meets
the following requirements:
It is recommended that shielded, twisted pair cables are used.
The minimum wire diameter depends on the line length.
Line lengths up to 1,500 m (4,921 ft): 0.51 mm (0.02 inch)
Line lengths above 1,500 m (4,921 ft): 0.81 mm (0.03 inch)
The maximum line length is limited.
Dual-core cable: 3,000 m (9,842 ft)
Multi-core cable: 1,500 m (4,921 ft)
The actual possible line length of the electrical circuit depends on the total capacitance and
resistance, and can be estimated using the following formula:
C
10000
f
C
CR
6
1065
L
+
−
×
×
=
L = Line length in meters
R = Total resistance in Ω (ohms)
C = Line capacitance in pF/m
C
f
= Maximum internal capacitance of the HART field devices located in the circuit, in pF
Avoid routing cables with other electrical cables (with inductive load, etc.) or near large electrical
equipment.