Configuration
IM/265D/V-EN-02 265Dx, 265VS 47
8.1.3 Transmitter with FOUNDATION Fieldbus communication
Parameters Factory settings
Measuring profile Pressure
Physical unit mbar/bar
Output scale 0 % Lower range limit (LRL)
Output scale 100 % Upper range limit (URL)
Output Linear
Upper alarm limit Upper range limit (URL)
Upper warning limit Upper range limit (URL)
Lower warning limit Lower range limit (LRL)
Lower alarm limit Lower range limit (LRL)
Hysteresis limit value 0.5 % of output scale
PV filter 0.125 sec.
Address Not required
Any or all of the configurable parameters listed above - including the lower and upper range
values - can be changed using any FOUNDATION Fieldbus-compatible configuration tool. Data
regarding flange type and material, O-ring materials, and type of filling liquid is stored in the
device.
Pos: 19.5 /Übersc hriften/1.1/1-spal tig/J - L/Konfigur ationsarten @ 0\mod_114052121 0140_3101.doc @ 3196
8.2 Configuration types
Pos: 19.6 /Konfi guration, Parametrier ung/Druck/Druck messumformer/Allgemei n/Konfigurations arten @ 2\mod_1150098392546 _3101.doc @ 29440
Pressure transmitters can be configured as follows:
• Configuration of the parameters for the lower and upper range values, without an LCD
display
• Configuration of the pressure transmitter using the LCD display (menu-controlled)
• Configuration with a handheld terminal
• Configuration using a PC/laptop via the graphical user interface (DTM)