Configuration
46 265Dx, 265VS IM/265D/V-EN-02
8.1.2 Transmitter with PROFIBUS PA communication
Parameters Factory settings
Measuring profile Pressure
Physical unit mbar/bar
Output scale 0 % Lower range limit (LRL)
Output scale 100 % Upper range limit (URL)
Output Linear
Upper alarm limit Upper range limit (URL)
Upper warning limit Upper range limit (URL)
Lower warning limit Lower range limit (LRL)
Lower alarm limit Lower range limit (LRL)
Hysteresis limit value 0.5 % of output scale
PV filter 0.125 sec.
Address 126
Any or all of the configurable parameters listed above - including the lower and upper range
values - can easily be changed using the PC operation software SMART VISION with DTM for
2600T. Data regarding flange type and material, O-ring materials, and type of filling liquid is
stored in the device.