EasyManua.ls Logo

ABB 265DS - Explosion protection data; Potentially explosive atmospheres

ABB 265DS
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Explosion protection data
64 265Dx, 265VS IM/265D/V-EN-02
Pos: 21.1 /Übersc hriften/1/D - F/Ex- technische Daten @ 0\mod_1132304 633775_3101.doc @ 3145
9 Explosion protection data
Pos: 21.2 /Übersc hriften/1.1/1-spal tig/D - F/Explosions gefährdete Atmosphären @ 2\mod_1149586014500_31 01.doc @ 28190
9.1 Potentially explosive atmospheres
Pos: 21.3 /==== Wechs el ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.d oc @ 3828
Change from one to two colu mns
Pos: 21.4 /Technisc he Daten / Datenblatt/ Druck/Druckmess umformer/265VS/Expl osionsgefährdete At mosphären/Explosi onsgefährdete Atmosphär en @ 20\mod_1208413159843_3 101.doc @ 180768
Transmitter with "Intrinsically safe EEx ia" type of explosion
protection in accordance with Directive 94/9/EC (ATEX)
Transmitter with 4 ... 20 mA output signal and HART communication:
Designation: II 1/2 GD T 50 °C EEx ia IIC T6
II 1/2 GD T 95 °C EEx ia IIC T4
Power supply and signal circuit with "Intrinsically safe, EEx ib IIB/IIC"
or "Intrinsically safe, EEx ia IIB/IIC" type of explosion protection, for
connection to supply units with the following maximum values:
II 1/2 GD T 50 °C EEx ia or ib IIC T6
II 1/2 GD T 95 °C EEx ia or ib IIC T4
Temperature class T4:
U
i
= 30 V
I
i
= 200 mA
P
i
= 0.8 W for T4 where Ta = -40 ... 85 °C
P
i
= 1.0 W for T4 where Ta = -40 ... 70 °C
For temperature class T6:
P
i
= 0.7 W for T6 where Ta = -40 ... 40 °C
Effective internal capacitance: C
i
= 10 nF
Effective internal inductance: L
i
0
Fieldbus transmitter (PROFIBUS PA / FOUNDATION Fieldbus):
Designation: FISCO field device
II 1/2G Ex ia IIC T6 or T4
II 1/2D Ex iaD 20 T50 °C or T95 °C
Power supply and signal circuit with "Intrinsically safe" type of
explosion protection, only for connection to supply units certified
according to the FISCO concept and with the following maximum
values:
U
i
= 17.5 V
I
i
= 500 mA
P
i
= 8.75 W
or connection to supply units or barriers with linear characteristics.
Maximum values:
U
i
= 24 V
I
i
= 250 mA
P
i
= 1.2 W
Effective internal inductance: L
i
= 10 μH,
Effective internal capacitance: C
i
= 5 nF
Permissible ambient temperature range depending on temperature
class:
Temperature class
Lower limit of
ambient
temperature
Upper limit of
ambient
temperature
T4 -40 °C (-40 °F) 85 °C (185 °F)
T5, T6 -40 °C (-40 °F) 40 °C (104 °F)
Category 3 transmitter for use in "Zone 2" as defined by
Directive 94/9/EC (ATEX)
Transmitter with 4 ... 20 mA output signal and HART communication:
Designation: II 3 GD T 50 °C EEx nL IIC T6
II 3 GD T 95 °C EEx nL IIC T4
Operating conditions:
Supply and signal circuit
(terminal signal ±): U
45 V
I
22.5 mA
Ambient temperature range:
Temperature class T4: Ta = -40 ... 85 °C
Temperature class T5 and T6: Ta = -40 ... 40 °C
Transmitter with "Flameproof EEx d" type of explosion
protection in accordance with Directive 94/9/EC (ATEX)
Transmitter with 4 … 20 mA output signal, HART communication,
and fieldbus transmitter (PROFIBUS PA / FOUNDATION Fieldbus)
Designation: II 1/2 G EEx d IIC T6
Operating conditions:
Ambient temperature range: -40 ... 75 °C

Table of Contents

Related product manuals